Here: Homepage -> Customer Service -> Cable Technology -> AVVR-300/300V Copper core PVC insulated cables technical parameters

AVVR-300/300V Copper core PVC insulated cables technical parameters

Form : http://www.chinadropwire.com/  Author:  Time:2008-12-25 10:09:09

AVVR-300/300V Copper core PVC insulated cables technical parameters

Cores× Sq.
(mm2)

Max. diameter of the conducor
(mm)

Iinsulation thickness
(mm)

Jacket thickness
(mm)

Average OD (mm)

 Resistance at 20℃(Ω/km)

Min. insulation resistance at 70℃
(MΩ·km)

MAX.

MIN.

Copper

Tinned copper

2×0.08

0.13

0.4

0.6

3.1
2.3×3.4

4.1
2.7×4.1

247

254

0.018

2×0.12

0.16

0.4

0.6

3.3
2.4×3.6

4.3
2.8×4.3

158

163

0.016

2×0.2

0.16

0.4

0.6

3.6
2.5×3.9

4.7
3.0×4.7

92.3

95

0.014

2×0.3

0.16

0.5

0.6

4.1
2.5×3.9

5.3
3.4×5.3

69.2

71.2

0.014

2×0.4

0.16

0.5

0.6

4.4
2.9×4.4

5.7
3.5×5.3

48.2

49.6

0.013

3×0.12

0.16

0.4

0.6

3.4

4.5

158

163

0.016

3×0.2

0.16

0.4

0.6

3.8

4.9

92.3

95

0.014

3×0.3

0.16

0.5

0.6

4.4

5.7

69.2

71.2

0.014

3×0.4

0.16

0.5

0.6

4.7

6.0

48.2

49.6

0.013

4×0.12

0.16

0.4

0.6

3.8

4.9

158

163

0.016

4×0.2

0.16

0.4

0.6

4.2

5.4

92.3

95

0.014

4×0.3

0.16

0.5

0.6

4.8

6.2

69.2

71.2

0.014

4×0.4

0.16

0.5

0.6

5.1

6.6

48.2

49.6

0.013

5×0.12

0.16

0.4

0.6

4.1

5.3

158

163

0.016

5×0.2

0.16

0.4

0.6

4.5

5.8

92.3

95

0.014

5×0.3

0.16

0.5

0.6

5.3

6.7

69.2

71.2

0.014

5×0.4

0.16

0.5

0.6

5.6

7.2

48.2

49.6

0.013

6~7×0.12

0.16

0.4

0.6

4.4

5.7

158

163

0.016

6~7×0.2

0.16

0.4

0.6

4.9

6.3

92.3

95

0.014

6~7×0.3

0.16

0.5

0.6

5.7

7.3

69.2

71.2

0.014

6~7×0.4

0.16

0.5

0.6

6.2

7.8

48.2

49.6

0.013

10×0.12

0.16

0.4

0.6

5.7

7.2

158

163

0.016

10×0.2

0.16

0.4

0.6

6.3

8.0

92.3

95

0.014

10×0.3

0.16

0.5

0.8

7.8

9.7

69.2

71.2

0.014

10×0.4

0.16

0.5

0.8

8.3

10.4

48.2

49.6

0.013

12×0.12

0.16

0.4

0.6

5.8

7.4

158

163

0.016

12×0.2

0.16

0.4

0.6

6.5

8.2

92.3

95

0.014

12×0.3

0.16

0.5

0.8

8

10.1

69.2

71.2

0.014

12×0.4

0.16

0.5

0.8

8.6

10.8

48.2

49.6

0.013

14×0.12

0.16

0.4

0.6

6.1

7.8

158

163

0.016

14×0.2

0.16

0.4

0.8

7.2

9.1

92.3

95

0.014

14×0.3

0.16

0.5

0.8

8.4

10.6

69.2

71.2

0.014

14×0.4

0.16

0.5

0.8

9.1

11.3

48.2

49.6

0.013

16×0.12

0.16

0.4

0.6

6.5

8.2

158

163

0.016

16×0.2

0.16

0.4

0.8

7.6

9.6

92.3

95

0.014

16×0.3

0.16

0.5

0.8

8.9

11.1

69.2

71.2

0.014

16×0.4

0.16

0.5

0.8

9.6

11.9

48.2

49.6

0.013

19×0.12

0.16

0.4

0.8

7.2

9.1

158

163

0.016

19×0.2

0.16

0.4

0.8

8.1

10.1

92.3

95

0.014

19×0.3

0.16

0.5

0.8

9.4

11.7

69.2

71.2

0.014

19×0.4

0.16

0.5

0.8

10.1

12.6

48.2

49.6

0.013

24×0.12

0.16

0.4

0.8

8.4

10.6

158

163

0.016

24×0.2

0.16

0.4

0.8

9.4

11.7

92.3

95

0.014

24×0.3

0.16

0.5

1.0

11.4

14.2

69.2

71.2

0.014

24×0.4

0.16

0.5

1.0

12.3

15.2

48.2

49.6

0.013

Statement: 
* conductor for the multi-annealing bare copper or tin plated copper strands
* PVC insulation
* PVC jacket
* film around the moisture-proof package
* tin copper braided shield

Use: 
 This applies to the wild product lines. Electrical Instrument telecommunications broadcasting, electronic equipment and automation devices, such as shielding lines.

The use of temperature:
* The length of wire to allow temperature is more than 70 ℃ 
* The laying of the cable, not lower than the temperature of -15 ℃ 
* Relative Humidity: 98%

Main technical parameters:
* rated voltage (AC 50 Hz): 380V DC: 500 V
* test voltage (AC 50 Hz): 2000V
* insulation resistance (20 ℃): not less than 2 M Ω km
* braided wire and cable general density of not less than 80 percent

Implementation of the standards: 
 JB 8734-1998   JIS C3662   
 JB 5023-1997   DIN VDE 0281   
 EC 227 

Model:
1.AVVR structural parameters
2.AVPV / SBVVP Copper core PVC insulated cables
3.AVPV SBVVP Copper core PVC insulated cables
4.AVR Copper core PVC insulated cables
5.AVRS Copper core PVC insulated cables